fbpx

Call Now 1800 247 266

  • call (1)

    1800 247 266

1.2MW Boiler – 600kW Dual Burner Containerised

Home > 1.2MW Boiler – 600kW Dual Burner Containerised
1.2MW Containerised Boiler hire rent cross hire services

The 1.2MW Container Boiler – 600kW Dual Burner is the ideal unit for large heating (LTHW), domestic hot water or combined requirement applications. It is a unit that brings together two 600kW boilers in one standard 20ft shipping container. It’s a fully-featured unit too, with a single controller to oversee all the equipment – including both boilers and the system pumps.

In addition, the 1.2MW Container Boiler – 600kW Dual Burner has a Boss Pressfill pressurisation unit and, for up to 1200kW of DHW duty, an external plate heat exchanger.

Run and Standby

The 1.2MW Container Boiler – 600kW Dual Burner provides a complete run and standby solution in the one unit. It houses two Ferroli Prextherm RSW600 boiler bodies, which are fired by dual burners inside the 20ft container. This lets the boiler offer 600kW of combined heating and DHW duty – with a standby unit on hand to take over if there is a fault with the main boiler body or burner.

For added resilience, the system pump is a twin-head inverter-driven unit. It means the pumps automatically switch over if there’s a fault with one of the pump units in addition to the boiler/burner backup. All this makes the 1.2MW Container Boiler – 600kW Dual Burner the perfect containerised boiler for critical applications if automatic switch-over to a standby system is a necessity.

 

GET A QUOTE!


  • This field is for validation purposes and should be left unchanged.
Nominal Output (Heating) 1220 kW
Temperature Range 60 - 95°C
Nominal Output (DHW) 1200 kW
Temperature Range 30 - 60°C
Power Supply 415v 3ph N+E 50Hz
Running Current 26 A
Plug Type 32A 5 Pin BS4343
Maximum Working Pressure 6 Bar
Safety Valves 3-7 Bar
Heat Exchanger Yes - Extenrnal
BMS Outputs Yes
Time Clock Yes
Frost Protection Yes
Design Flow 51,600 ltrs/hr
Pump Capacity 1.2 Bar
Variable Temperature Control Yes
Height of Flue Above Ground Level 3,400mm
Expansion Vessel 1,000 ltrs
DHW Circulation System Yes
Flexible Hose Connections PN16 Flange
Water Connections Flow / Return, 4” DN100
Fuel Type Diesel Oil or Natural Gas
Fuel Connections External Oil Tank or 3” Gas Train
Fuel Consumption 128 ltrs/hr (Oil)
Noise Level 46 dBA @ 10 mtrs
Handling Options Fork Pockets, Lifting Points (to be lifted with long chains)
Weight (Dry) 6,700 kg
Dimensions (WxDxH) 2,430 x 6,100 x 3,100mm

Alternatively please fill out the form below.