1.2MW Boiler – 600kW Dual Burner Containerised
The 1.2MW Container Boiler – 600kW Dual Burner is the ideal unit for large heating (LTHW), domestic hot water or combined requirement applications. It is a unit that brings together two 600kW boilers in one standard 20ft shipping container. It’s a fully-featured unit too, with a single controller to oversee all the equipment – including both boilers and the system pumps.
In addition, the 1.2MW Container Boiler – 600kW Dual Burner has a Boss Pressfill pressurisation unit and, for up to 1200kW of DHW duty, an external plate heat exchanger.
Run and Standby
The 1.2MW Container Boiler – 600kW Dual Burner provides a complete run and standby solution in the one unit. It houses two Ferroli Prextherm RSW600 boiler bodies, which are fired by dual burners inside the 20ft container. This lets the boiler offer 600kW of combined heating and DHW duty – with a standby unit on hand to take over if there is a fault with the main boiler body or burner.
For added resilience, the system pump is a twin-head inverter-driven unit. It means the pumps automatically switch over if there’s a fault with one of the pump units in addition to the boiler/burner backup. All this makes the 1.2MW Container Boiler – 600kW Dual Burner the perfect containerised boiler for critical applications if automatic switch-over to a standby system is a necessity.
Require Our Services? Get In Touch
Alternatively please request a quote below.
Nominal Output (Heating) | 1,220 kW |
Temperature Range | 60 - 95°C |
Nominal Output (DHW) | 1200 kW |
Temperature Range | 30 - 60°C |
Power Supply | 415v 3ph N+E 50Hz |
Running Current | 26 A |
Plug Type | 32A 5 Pin BS4343 |
Maximum Working Pressure | 6 Bar |
Safety Valves | 3-7 Bar |
Heat Exchanger | Yes - Extenrnal |
BMS Outputs | Yes |
Time Clock | Yes |
Frost Protection | Yes |
Design Flow | 51,600 L/h |
Pump Capacity | 1.2 Bar |
Variable Temperature Control | Yes |
Height of Flue Above Ground Level | 3,400mm |
Expansion Vessel | 1,000 L |
DHW Circulation System | Yes |
Flexible Hose Connections | PN16 Flange |
Water Connections | Flow / Return, 4” DN100 |
Fuel Type | Diesel Oil or Natural Gas |
Fuel Connections | External Oil Tank or 3” Gas Train |
Fuel Consumption | 128 L/h (Oil) |
Noise Level | 46 dBA @ 10 M |
Handling Options | Fork Pockets, Lifting Points (to be lifted with long chains) |
Weight (Dry) | 6,700 Kg |
Dimensions (WxDxH) | 2,430 x 6,100 x 3,100 mm |