250kW Air Cooled Chiller
Require Our Services? Get In Touch
Alternatively please request a quote below.
Detail | 250kW Chiller | |
Performance Data | Chiller Cooling Capacity | 250 [kW] |
Inlet Temperature | 12 [°C] | |
Outlet Temperature | 7 [°C] | |
Ambient | 35 [°C] | |
Compressors | 4 | |
Compressor Type | Scroll | |
Capacity Steps | 4 | |
Noise Level | 60 [dB(A)] @ 10 metres | |
Sound power | 92 [dB(A)] | |
Circuits | 2 n. | |
DIMENSIONS AND WEIGHTS | ||
Dimensions (L x H x D) | 4,550 x 1,350 x 2,440 [mm] | |
Dry Weight | 1,960 [kg] | |
Control | Automatic Programme | |
Buffer Tank Capacity | 500 [L] | |
Water Connection | 4" Bauer Male & Female | |
Water Pump | Yes | |
Refrigerant | Type | R410a |
No of Circuits | 2 | |
Evaporator | Type | Plate |
No of Circuits | 2 | |
Design Flow | 44.3 [m³/h] | |
Pressure Drop | 78 [kPa] | |
Condensor | Fan Quantity | 4 |
Fan Type | Axial | |
Electrical | Electrical supply | 400 V / 3 ph / 50 Hz, N + Eth |
Power Input | 80 [kW] | |
Full Load Amps | 194.6 [A] | |
Unit Connection | Hard Wired |