500kW Air Cooled Chiller
500kW portable chiller suitable for a wide variety of large temporary cooling applications, from process cooling to air conditioning for larger buildings; fit for emergency recovery or planned maintenance.
Can be paired with air handling units to provide a complete air conditioning system for temporary events or semi permanent applications.
Steel framed for resilience and ease of delivery & installation.
Fully equipped with a water strainer; an electronic expansion valve; a condensing coil grid with metallic filter; a water expansion vessel; and a 3-bar water pump and 500 litre buffer tank, water outlet temperature regulator, automatic fan circuit breaker & a fan speed regulator, internal fan protection grid & electric board heater.
Require Our Services? Get In Touch
Alternatively please request a quote below.
Duty | 500kW |
Inlet Temperature | 12°C |
Outlet Temperature | 7°C |
Ambient | 30°C |
Compressor Power | 202.8 kW |
EER | 2.5 |
Compressors | 6 |
Compressor Type | Scroll |
Capacity Steps | 6 |
Noise Level | 60 dBA @ 10 Metres |
Dry Weight | 3500kg |
Dimensions | (LxWxH) 5250 x 2505 x 2620 mm |
Control | Automatic Programme |
Buffer Tank Capacity | 500 Litres |
Water Connection | 4” Bauer Male & Female |
Water Pump | Yes – Lowara FHE60-160/110 |
Refrigerant | Type R410a |
No. Of Circuits | 2 |
Evaporator Type | Plate |
No Of Circuits | 2 |
Design Flow | 82.7m3/hour |
Pressure Drop | 35 kPa |
Max System Pressure | 208 kPa |
Condensor Fan Quantity | 8 |
Fan Type | Axial |
Max Air Volume | 15.5 m3/second |
Power Supply | 415vAC 3Ø, N + Eth |
Full Load Amps | 394 Amps |
Unit Connection | Hard Wired |
Power Consumption | 231 kW/h |
Start Amps | 648 Amps |