The 600kW Air Cooled Chiller can be used for the most complete range of cooling applications; from air conditioning to process cooling and even ice rink creation. It can also be used as part of a standalone air conditioning system suitable for temporary events or permanent installation when combined with air handling units.
Require Our Services? Get In Touch
Alternatively please request a quote below.
Nominal Cooling Duty | 600 kW |
Design Duty | 746 kW |
Inlet Temperature | +12°C |
Outlet Temperature | +7°C |
Ambient | +35°C |
Compressor Power | 263.5 kW |
EER | 2.8 |
Noise Levels | 64.1 dBA @ 10 Metres |
Control | Automatic Programmer |
Power Consumption | 263.57 kW/h |
Water Connections | 6” Bauer Male & Female |
Buffer Vessel | 500 Litres |
Water Pump | NSCE 80-160/185/P25VCCZ |
Compressors | 8 |
Compressor Type | Scroll |
Capacity Steps | 8 |
Refrigerant Type | R410a |
No. of Circuits | 4 |
Noise Level | 64.1 dBA @ 10m |
Evaporator Type | Plate |
Number of Circuits | 4 |
Design Flow | 128.3 m³/h |
Pressure Drop | 54 kPa |
Max System Pressure | 4 bar |
Fan Quantity | 8 |
Fan Type | Axial |
Electrical Power | 415vAC 3Ø, N + Eth |
Full Load Amps | 589.6 Amps |
Start Amps | 929 A |
Unit Connection | Hardwired |
Dry Weight | 7,500 Kg |
Dimensions (WxLxH) | 2,384 x 6,527 x 2,555 mm |